background image

Publication DNET-UM072C-EN-P - July 2004

Determine Power Requirements 4-9

Figure 4.6 Two End-Connected Power Supplies, KwikLink Cable (Flat)

NEC/CE Code Maximum
Current Limit

Exceeds NEC CL2/CECode 4A limit.

Length of trunk line, meters (feet)

C

ur

rent

(amp

er

es)

Network
length
m (ft)

Maximum
current (A)

0 (0)

8.00*

20 (66)

8.00*

40 (131)

8.00*

60 (197)

8.00*

80 (262)

8.00*

100 (328)

8.00*

120 (394)

8.00*

140 (459)

7.35*

160 (525)

6.43*

180 (591)

5.72*

200 (656)

5.16*

Network
length
m (ft)

Maximum
current (A)

220 (722)

4.69*

240 (787)

4.30*

260 (853)

3.97

280 (919)

3.69

300 (984)

3.44

320 (1050)

3.23

340 (1115)

3.04

360 (1181)

2.87

380 (1247)

2.72

400 (1312)

2.59

420 (1378)

2.46