Publication DNET-UM072C-EN-P - July 2004

5-4 Correct and Prevent Network Problems

bus traffic problems

•

nodes stop communicating

•

device times out

•

check scanner configuration to ensure scan
rate is set correctly

−

inter-scan/delay scan interval too short
can cause device timeouts

−

inter-scan/delay scan interval too long
can reduce system performance and
make inefficient use of available
bandwidth

•

check change-of-state devices consuming
excessive bandwidth

•

increase production inhibit time or change
these devices to polling, cyclic, or bit strobe
communication

•

check for nodes with excessive bandwidth or
a much-higher than average MAX value

bus power problems

•

nodes near the end of the trunk line stop
communicating after operating normally

•

the network communicates only when the
number of nodes is decreased or the trunk
length is reduced

•

check network power voltage at the node

•

check common mode voltage

•

check for output devices (e.g., contactors)
powered from the network

•

check for interference caused by network
cables routed too closely to high-voltage and
RF lines

•

use an oscilloscope to check the power
supply trace for ripple increasing over time
against the baseline

•

check cables for intermittent operation by
shaking, bending or twisting the suspected
cable or connection and checking
peak-to-peak voltages

shield voltage problems

•

nodes operate intermittently

•

properly configured slave devices are not
detected by the scanner

•

check shield voltage

•

check for additional V- or shield wire
connections

•

check for loose connections (in particular,
field-attachable connections)

•

ensure that only shield and V- wires are
connected together at earth ground and the
power supply

problem

symptom

do this