3-14 Make Cable Connections
– You must cut or heat shrink the drain wire when you use round
5-wire (thin) drop cable.
Install end caps
Each KwikLink terminator module is supplied with an end cap designed to
cover the exposed end of the cable. To install the end cap:
1. Fit the end cap (1485A-CAP) on the cable as keyed. Align the end cap
posts with the receptacles in the lower IDC base and press down until
the end cap is firmly seated (the upper surface of the posts will be flush
with the upper surface of the base).
2. Close the IDC base and continue with the connection process as
illustrated on page 3-10.
IMPORTANT
When installing an end cap on the other end of the cable,
note that the guide receptacles are on the upper portion of
the IDC base.
41809
red
white
blue
black
red
white
blue
black
The round 4-wire
KwikLink drop cable
(gray) has no drain wire.
To use round 5-wire (thin) drop
cable, bend back and heat shrink,
or cut, the drain wire.
Use only with
KwikLink
Wire
Color
Wire
identity
Use
Flat
white
CAN_H
signal
signal
blue
CAN_L
signal
signal
bare
drain
shield
n/a
black
V-
power
power
red
V+
power
power
Align the end cap posts with
receptacles in the base.
30480-M