Use the look-up method – Rockwell Automation DeviceNet Media Design Installation Guide User Manual

Page 81

Advertising
background image

Publication DNET-UM072C-EN-P - July 2004

Determine Power Requirements 4-3

Use the Look-up Method

To determine if you have adequate power for the devices in your cable system,
see the following examples and figures. You have enough power if the total
load does not exceed the value shown by the curve or the table.

In a worst-case scenario, all of the nodes are together at the opposite end of
the power supply.

TIP

This method may underestimate the capacity of your
network by as much as 4 to 1. See the following section to
use the full-calculation method if your supply does not fit
under the curve.

41710

For this configuration example

Flat cable
uses figure

Thick
cable uses
figure

Thin cable
uses figure

One power supply (end-connected)

Figure 4.2

Figure 4.1

Figure 4.7

One power supply (middle-connected)

Figure 4.2

Figure 4.1

Figure 4.7

NEC/CECode current boost configuration (V+
cut)

Figure 4.2

Figure 4.1

Figure 4.7

Two power supplies (end-connected)

Figure 4.6

Figure 4.5

*

Two power supplies (not end-connected)

Figure 4.4

Figure 4.3 *

* You can draw as much as 3A from a thin cable trunk line if the power supply separation is

below 70m (230 ft).

Advertising