Get Started 1-5
Basic DeviceNet network
Understand the topology
The DeviceNet cable system uses a trunk/drop line topology.
This figure shows a basic DeviceNet network and calls out its basic components.
TR
TR
Power
Supply
TR
terminating resistor
device or node
1
3,4
2
2
Checklist
5
trunk line
drop lines
41829
D
Understand the
Media
1
You must terminate the trunk line at both ends
with 121
Ω
, 1%, 1/4W or larger terminating
resistors.
device or node
TR
TR
trunk line
drop line
TR = terminating resistor
41826