3-10 Make Cable Connections

4. Make the connection to the trunk line last.

Install KwikLink Cable and
KwikLink Heavy-Duty
Connectors

Install KwikLink cable with the wider, flat edge of the cable on the bottom.

Follow these steps to properly install KwikLink cable into a connector:

1. Lay the cable in the hinged base, paying attention to the keyed profile.

The unkeyed edge is closer to the hinge; the keyed edge is toward the
latch.

IMPORTANT

Follow the wiring diagrams for each connection, and make
sure you do not exceed the maximum allowable length
from the device connection to the trunk connection.

IMPORTANT

1485-P1Kxxx cable cannot be used with KwikLink
heavy-duty connectors.

IMPORTANT

Prior to closing the connector, make sure the IDC blades
do not protrude from the housing. If the blades are
exposed, gently push them back into the base. In the event
that the blades do not retract easily (or retract only
partially), verify that the IDC screws are not partially
driven.

flat edge

keyed edge

41607

Class 1 (CL1) KwikLink Cable

Spool Size

Catalog Number

75 m (246 ft)

1485C-P1E75

200 m (656 ft)

1485C-P1E200

420 m (1378 ft)

1485C-P1E420

30474-M

keyed edge is toward
the latch

latch

Class 2 (CL2) KwikLink Cable

Spool Size

Catalog Number

75 m (246 ft)

1485C-P1G75

200 m (656 ft)

1485C-P1G200

420 m (1378 ft)

1485C-P1G420