Publication DNET-UM072C-EN-P - July 2004

Get Started 1-19

A sample curve for a single, end-connected power supply is shown on the next
page.

Figure 1.1 One Power Supply (End Segment) KwikLink Cable (Flat)

C

ur

rent

(a

m

per

es)

Length of trunk line, meters (feet)

NEC/CE Code Maximum
Current Limit

Network
Length
m (ft)

Maximum
Current (A)

0 (0)

8.00

*

20 (66)

8.00

*

40 (131)

7.01

*

60 (197)

4.72

*

80 (262)

3.56

100 (328)

2.86

120 (394)

2.39

140 (459)

2.05

160 (525)

1.79

180 (591)

1.60

200 (656)

1.44

Network
Length
m (ft)

Maximum
Current (A)

220 (722)

1.31

240 (787)

1.20

260 (853)

1.11

280 (919)

1.03

300 (984)

0.96

320 (1050)

0.90

340 (1115)

0.85

360 (1181)

0.80

380 (1247)

0.76

400 (1312)

0.72

420 (1378)

0.69

Exceeds NEC CL2/CECode 4A limit.

41932

IMPORTANT

This configuration assumes all nodes are at the opposite
end of the cable from the power supply.