Use terminating resistors, Ground the network, Diagnose power supply problems – Rockwell Automation DeviceNet Media Design Installation Guide User Manual

Page 111

Advertising
background image

Publication DNET-UM072C-EN-P - July 2004

Correct and Prevent Network Problems 5-7

Use Terminating Resistors

The DeviceNet network may operate unpredictably without terminating
resistors installed at each end of the trunk cable. You can order terminating
resistors, part number 1485A-C2, from your local Rockwell Automation
distributor.

To install terminating resistors:

1. Attach a 121

, 1%, 1/4W or larger terminating resistor at each end of

the trunk cable, across the blue (CAN_H) and white (CAN_L) wires of
the cable.

2. Verify resistor connection.

a. Disconnect DeviceNet power.
b. Measure the resistance across the blue (CAN_H) and white

(CAN_L) wires of the cable. Resistance should equal approximately
50 - 60

Ω.

Resistance will approach 50

as more devices are

connected to the network.

Ground the Network

You must ground the DeviceNet cable at only one location, closest to the
center of the network.

To ground the network:

1. Using an 8 AWG (10mm

2

) wire up to a maximum of 3m (10 ft.) in

length, connect the following:

a. Connect the network shield and drain wires to an earth ground.
b. Connect the V- conductor (black wire) of the trunk cable to an earth

ground.

c. Connect the DC ground of the power supply to an earth ground.

Diagnose Power Supply
Problems

The DeviceNet network requires 24V dc power. Ensure that the power supply
you are using meets the following requirements.

The DeviceNet power supply must:

be sized correctly to provide each device with its required power

be rated 24V dc (+/- 1%)

have its own current limit protection

have a rise time of less than 250mS to within 5% of its rated output
voltage

Advertising