Cables exit in the center – Rockwell Automation LDC Iron Core Linear Servo Motors User Manual
Page 43
Advertising
Rockwell Automation Publication LDC-UM001B-EN-P - March 2011
43
Wire the LDC-Series Linear Motor Chapter 5
Cables Exit in the Center
If mounting coils in tandem, such that the power cables exit in the center as
shown, use the following table to find the mounting distance and the phase
wiring.
Figure 4 - Mounting Two Coils with Cables Exit in the Center
Coil #1
Coil #2
Coil #1 is the master.
Hall Effect
Module
L
Table 6 - Phase Wiring for Center-exit Power Cables
L
mm (in.)
Coil # 1
Master
(1)
Coil # 2
Slave
(2)
Amplifier
Phase
133.33 (5.249)
Red
Black
U
White
White
V
Black
Red
W
(1) Master has Hall effect module.
(2) Slave has no Hall effect module.