Additional adjustments for cooling plate option, Click the limits tab – Rockwell Automation LDC Iron Core Linear Servo Motors User Manual

Page 60

Advertising
background image

60

Rockwell Automation Publication LDC-UM001B-EN-P - March 2011

Chapter 6 Configure and Start Up the LDC-Series Linear Motor

Additional Adjustments for
Cooling Plate Option

If your linear servo motor has the cooling plate option installed, catalog number
LDC-

xxxxxx-CP, follow these steps to adjust Continuous Torque/Force Limit.

1.

Click the Limits tab.

2.

Set the Continuous Torque/Force Limit to reflect the motor cooling
configuration.

For linear motors, this field data entry is limited to integer values from
0…150%.

Cooling Option Used

Value

No cooling plate

0…100%

Cooling plate with forced air

0…120%

Cooling plate with forced water

0…150%

IMPORTANT

Increasing or decreasing the motor continuous current rating does not
change the drives’ continuous current limiting.