Additional adjustments for cooling plate option, Click the limits tab – Rockwell Automation LDC Iron Core Linear Servo Motors User Manual
Page 60
60
Rockwell Automation Publication LDC-UM001B-EN-P - March 2011
Chapter 6 Configure and Start Up the LDC-Series Linear Motor
Additional Adjustments for
Cooling Plate Option
If your linear servo motor has the cooling plate option installed, catalog number
LDC-
xxxxxx-CP, follow these steps to adjust Continuous Torque/Force Limit.
1.
Click the Limits tab.
2.
Set the Continuous Torque/Force Limit to reflect the motor cooling
configuration.
For linear motors, this field data entry is limited to integer values from
0…150%.
Cooling Option Used
Value
No cooling plate
0…100%
Cooling plate with forced air
0…120%
Cooling plate with forced water
0…150%
IMPORTANT
Increasing or decreasing the motor continuous current rating does not
change the drives’ continuous current limiting.