Configure and Start Up the LDC-Series Linear Motor Chapter 6

Set Up the Connection to an
Ultra3000 Drive

This procedure configures the Ultra3000 drive for your linear motor and encoder
combination.

For help using Ultraware software as it applies to setting up your linear motor,
refer to

Additional Resources

on

page 9

. This procedure assumes you are familiar

with Ultraware software.

1.

Open your Motor Configurator Utility.

2.

Select the linear motor catalog number.

3.

From the Edit menu, choose Duplicate.

4.

Rename the Model.

5.

Click Encoder Type and select either Incremental or Sin/Cos.

6.

Click Lines Per Meter and enter the value.

The following tables list typical values for lines per meter.

Figure 11 - Incremental Encoder

Figure 12 - Sin/Cos Encoder

7.

Click Close.

8.

Open your Ultraware software.

9.

Configure your Ultra3000 drive.

Incremental

Sin/Cos

Resolution

Value

Encoder Scale Pitch

Value

10 µm

25,000

100 µm

10,000

5 µm

50,000

40 µm

25,000

2 µm

125,000

20 µm

50,000

1 µm

250,000

0.5 µm

500,000

0.1 µm

2,500,000