FanMaster Installation

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

Installation Considerations

Consider and plan for the following when installing FanMaster for
integration with an AHU:

The existing BAS control supply fan start/stop signal. Two relays are
provided for interfacing to the BAS fan start/stop signal. The relay
installed in the FanMaster enclosure accommodates a 120V AC signal.
A second relay is shipped loose and accommodates a 24V AC signal. If
a signal other than 24V or 120V AC is used, you must purchase and
install the appropriate relay separately. The Allen-Bradley 700-HK
family of relays provides coil voltages from 6V AC…240V AC or 6V
DC…48V DC. More information is provided on the Allen-Bradley web
site at:

http://www.ab.com/en/epub/catalogs/12768/229240/229266/

229643/229701/tab3.html

The existing BAS outside air damper position control signal (used with
constant ventilation option only). FanMaster provides I/O connections
for a 4…20 mA signal only. If the BAS control signal is 0…10V DC or
0…135 Ohms, a converter adapter must be purchased separately for
both the input and output signals.

When installing FanMaster with a Variable Frequency Drive, the
following firmware revisions must be used:

PowerFlex 400, v1.004 and later

PowerFlex 70EC v3.001 and later

PowerFlex 700VC v4.001 and later

PowerFlex 753 v1.005 and later

Installation Requirements

Power Source for FanMaster

120V AC, 10 Amp (min.) grounded service.

Tools Required for Installation

Variable speed drill

Sheet metal drill bits

Various screwdrivers

Various wrenches (open, socket and/or torque)

Conduit cutting and bending tools (optional, for permanent
installations)

Wiring Specifications

Important: All power, I/O and signal wiring is customer supplied.

All wire to be Stranded, copper, 600V/105 °C (194 °F) insulation.

Terminal(s) Description

Max. Wire Size Min. Wire Size

Torque

L, N

Power

10 AWG

22 AWG

1.0 N•m (9.0 lb•in)

GND

Ground

6 AWG

16 AWG

2.3 N•m (20.4 lb•in)

I/O and Signal

12 AWG

22 AWG

0.6…0.8 N•m (4.5…7.1 lb•in)