Rockwell Automation FANM FanMaster Energy Saving Package User Manual

Page 49

Advertising
background image

FanMaster Configuration and Start Up

3-13

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

41. If a CO

2

sensor is installed, press the value next to the “CO2 Alarm

Setpoint ppm” and enter the CO

2

parts per million (ppm) at which the

an alarm will display on the PanelView screen, the fault indicator lamp
on the front of the unit will turn on and the FanMaster Faulted signal
will be set to “Faulted”, indicating that the high CO

2

level threshold has

been exceeded.

42. Press Next. The Supply Fan Setup screen displays.

43. Read and complete the tasks in steps 1 and 2 on the Supply Fan Setup

screen to set the supply fan drive parameters to the correct values.

For PowerFlex 400 drives, complete the tasks on the Supply Fan Setup
screen only. For PowerFlex 70EC, 700VC, or 753 drives, complete the
tasks on the screen and the appropriate steps detailed on the following
pages, only when instructed to do so.

PowerFlex 753 Drives Only

Advertising