FanMaster Installation

2-11

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

Wire the FanMaster and Drive (if Installed)

Refer to the

FanMaster Diagrams

contained in Appendix B for wiring and

connection details.

1. For permanent installations, determine where conduit will be routed and

prepare the FanMaster enclosure for conduit connections.

For NEMA/UL Type 1 enclosures, remove the metal plugs in the
pre-located openings in the enclosure for conduit connections.

For NEMA/UL Type 4 enclosures, drill the desired openings in the
enclosure to accommodate conduit connections.

2. Open the FanMaster enclosure and verify that circuit breaker 1 (CB1) is

in the “off” position.

3. Route the power wires through the appropriate conduit (if used) and

connect to terminals L, N and G on terminal block 1 (TB1). Refer to

Wiring Specifications on page 2-2

for power wire size.

!

ATTENTION: Do not route signal and control wiring with
power wiring in the same conduit. This can cause interference
with operation. Failure to observe this precaution could result in
damage to, or destruction of, the equipment.

!

ATTENTION: Protect the contents of the enclosure from metal
chips and other debris while removing the conduit opening plugs.
Failure to observe this precaution could result in damage to, or
destruction of, the equipment.

FANMASTER

FAULTED

FANMASTER

OVERRIDE

OFF ON

PanelView C600

NEMA/UL Type 1 Enclosure Shown