A-2

Specifications and City Climate Profiles

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

Inputs and Outputs

Inputs:

Supply Air Temp. @ 4…20 mA = 0°…100°C (32°…212°F)

Mixed Air Temp. @ 4…20 mA = 0°…100°C (32°…212°F)

CO

2

@ 4…20 mA = 0…2000 ppm

Damper Position Switch (when not using constant vent. option) = DC
contact closed when open > minimum (Economizer active)

BAS Start (full only) = 115V AC or 24V AC signal

Current Switch (evaluation unit only) = DC contact closed when fan
running

Supply Fan Drive Running = Contact on drive closed when supply fan
drive running

Supply Fan Drive Status and Speed Feedback (via Modbus RTU)

Return Fan Drive Status and Speed Feedback (via Modbus RTU, when
installed)

Outside Air Damper Command from BAS (required only w/constant vent.
option) @ 4…20 mA = 0…100% open command

Pressure (optional w/pressure override) @ 4…20 mA = -0.100…0.100
InWC building pressure to outside pressure difference

Outputs:

High CO2 Alarm = Isolated contact closed

Supply Fan Proof of Flow = Isolated contact closed

FanMaster Not Faulted = Isolated contact closed

Damper Override (force outside air damper closed) - (used only when not
using constant vent. option) = Isolated contact closed

Damper Command to Outside Air Damper - connect at supply fan drive
analog output 1 terminals (required only w/constant vent.) @ 4…20 mA =
0…100% open command

Supply Fan Start/Stop and Speed Reference (via Modbus RTU)

Return Fan Start/Stop and Speed Reference (via Modbus RTU, when
installed)

Instrumentation

Temperature Transmitter (2): 0°…100° C (32°F

212°F) Duct Insertion

CO

2

Sensor: 0

2000 ppm, Duct Mount

Damper Switch:

Type: Mechanical

Rating: 5 A, 120/250V AC

Operation: SPDT

Angle: N.O. makes 20 degrees above horizontal, breaks 15 degrees
below horizontal

Operating Temp.: -30°…130°F (-34°…54°C)

Enclosure: UL 94V-0 flammability rating

Optional
Instrumentation

Current Switch (provided w/evaluation unit only):

Type: AC/DC

Switch Voltage Max.: 30V AC/40V DC

Current Max.: 500 mA

Voltage on @ 24V DC , 150 mA: < 0.1V

Input Current Min.: 1.5 A

Input Current Max.: 200 A

Recommended Modus T30 or M30 Differential Pressure Transmitter
(customer supplied):

Supply Voltage: 11…32V DC

Power: 0.9 VA

Analog Output: 4…20 mA limited to approx. 3.85 mA at low end of span,
approx. 25 mA at upper end

Overpressure: 8 x pressure range or 8'' W.C. (1992.8 Pa), whichever is
greater

Operating Temp.: 0°…45°C (32°…115°F)

Medium: Air or inert gases