FanMaster Diagrams

B-11

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

Figure B.10 Interconnect Diagram for PowerFlex 700VC Drive - Sheet 1

FanMaster

TB2

TB3

TB1

TB2

TB2

Supply Fan Drive

PowerFlex 700VC

Drive I/O TB

16

15

Drive Running

20-COMM-H TB

RS-485 cable

Signal = 120V AC

Signal = 4-20 mA

+

Optional Position
Command to Damper

Drive I/O TB

7

6

A.O. 1

A.O. 1 Com

PowerFlex 700VC

Signal = RS-485

Signal = 24V DC

Damper Position
Switch (In Econ. Mode)

BAS Outside Air
Damper Override Control

Black

Red

Line

Common

Signal = Customer Selected

Customer Supplied Line

Customer Supplied Nuetral

119

120

100

105

135

N

Fan Running Input

120V AC Input

L

N

G

Factory Installed Jumpers

Customer
Supplied
120V AC,
50/60 Hz
Power

Econ. Mode Switch +24V DC

Input Signal for Econ. Mode Switch

BAS Damper Override
Control Output

A

A

Notes:
1. All power, I/O and signal wire is customer supplied.
2. Non-shielded wires to be Belden No. 3105A or equal.
3. Shielded cable to be a Belden No. 3106A or equal.

Return Fan Drive

(Optional)

To Sheet 2

To Sheet 2

20-COMM-H TB

CGND

SHLD

COM

B

A

TERM

GND

SHIELD

COM

B

A

TERM

GND

SHIELD

COM

B

A

TERM