Figure b.10, B-11, Fanmaster diagrams b-11 – Rockwell Automation FANM FanMaster Energy Saving Package User Manual
Page 85

FanMaster Diagrams
B-11
Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -
Publication FANM-IN001B-EN-P – December, 2009 PN-65329
Figure B.10 Interconnect Diagram for PowerFlex 700VC Drive - Sheet 1
FanMaster
TB2
TB3
TB1
TB2
TB2
Supply Fan Drive
PowerFlex 700VC
Drive I/O TB
16
15
Drive Running
20-COMM-H TB
RS-485 cable
Signal = 120V AC
Signal = 4-20 mA
+
–
Optional Position
Command to Damper
Drive I/O TB
7
6
A.O. 1
A.O. 1 Com
PowerFlex 700VC
Signal = RS-485
Signal = 24V DC
Damper Position
Switch (In Econ. Mode)
BAS Outside Air
Damper Override Control
Black
Red
Line
Common
Signal = Customer Selected
Customer Supplied Line
Customer Supplied Nuetral
119
120
100
105
135
N
Fan Running Input
120V AC Input
L
N
G
Factory Installed Jumpers
Customer
Supplied
120V AC,
50/60 Hz
Power
Econ. Mode Switch +24V DC
Input Signal for Econ. Mode Switch
BAS Damper Override
Control Output
A
A
Notes:
1. All power, I/O and signal wire is customer supplied.
2. Non-shielded wires to be Belden No. 3105A or equal.
3. Shielded cable to be a Belden No. 3106A or equal.
Return Fan Drive
(Optional)
To Sheet 2
To Sheet 2
20-COMM-H TB
CGND
SHLD
COM
B
A
TERM
GND
SHIELD
COM
B
A
TERM
GND
SHIELD
COM
B
A
TERM