Rockwell Automation FANM FanMaster Energy Saving Package User Manual

Page 57

Advertising
background image

FanMaster Configuration and Start Up

3-21

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

Note: When in heating mode, the supply fan speed will typically be set
based on the difference in temperature (Delta-T) between the mixed air and
supply air (as illustrated, using default values, in

Figure 3.3

and

Figure 3.4

below) unless the supply air temperature exceeds the high limit override (is
greater than the default value of 155° F). If the supply air temperature
exceeds the high limit override value, the fan speed will increase to the VFD
output maximum value (for heating setup).

Figure 3.3

Example Two-State Heating Setup

Figure 3.4

Example Proportional Heating Setup

Delta-T

F

an Speed (%)

Two-State Heating Setup

Delta-T

Min

Delta-T

Max

VFD
Output
Min

VFD
Output
Max

(Supply Air - Mixed Air Temp.)

10 20 30 40 50

100

75

50

25

0

Proportional Heating

Delta-T

Min

Delta-T

Max

VFD
Output
Min

VFD
Output
Max

F

a

n Speed (%)

Delta-T

(Supply Air - Mixed Air Temp.)

10 20 30 40 50

100

75

50

25

0