3-2

FanMaster Configuration and Start Up

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

Gather and Record Data

Gather the following data in order to successfully configure and start up the
FanMaster. Record the actual data for your installation in the table below
and save the table for your records.

Table 3.A Installation Data

Step Data Required

Default Value

Actual

8

City climate profile (refer to

City Climate Profiles on page A-3

for a complete list of available

cities):
Note: If an acceptable climate profile is not included in the list in Appendix A, you can use the
User City Weather Data Setup screen (described on page

C-14

) to create and save a climate

profile for your location.

Chicago

9

Supply fan motor nameplate horsepower (HP) rating

10

10

Supply fan motor nameplate full load amps (FLA) rating

12.2

11

AHU CFM (If set to “0” in configuration, value will be auto calculated based on 2,000 CFM per
1 HP)

30,000

13

Return fan motor nameplate horsepower (HP) rating (if installed)

5

14

Return fan motor nameplate full load amps (FLA) rating (if installed)

6.1

15

Electrical cost in dollars per kWh

0.0891

16

Natural gas cost in dollars per MMBTU

8.50

17

Heating efficiency for your system

87%

18

Outside air damper minimum open position

10%

19

Coolant type used

Glycol or Water

29

Is heating proportional (heat source level is varied) or two-state (heating is on or off)?

Heating Prop

30

Is cooling proportional (cooling source level is varied) or two-state (cooling is on or off)?

Cooling Prop

31

The system uses a pressure sensor (yes/no)?

No Pressure

32

The system uses on-demand ventilation (CO

2

sensor is installed) or constant ventilation

(Constant Vent.)?

Demand Vent.

33

The system uses a CO

2

sensor (yes/no)?

CO2 (yes)

35

The AHU has a heating system (yes/no)?

Yes / Mech Heat

36

The AHU has a cooling system (yes/no)?

Yes / Mech Cool

37

FanMaster will be allowed to override the BAS control of the outside air damper (yes/no)?

Yes / Damper Override

38

If FanMaster will override the BAS control of the outside air damper, the percent (10…50) of
time the outside air damper will be closed during a 20 minute cycle time. 10% = 2 minutes
closed / 18 minutes open. 50% = 10 minutes closed / 10 minutes open.

50%

39

If a pressure sensor is used, the inWC value below which the supply fan speed should
increase so pressure is maintained.

-0.010

40

If a CO

2

sensor is installed, the CO

2

parts per million (ppm) at which outside air ventilation

should occur.

700

41

If a CO

2

sensor is installed, the CO

2

parts per million (ppm) at which a high CO

2

alarm will

occur.

800

49a The difference in temperature between the mixed air and supply air at or below which the

drive will run the supply fan at the minimum speed when cooling the conditioned space.

5

49b The difference in temperature between the mixed air and supply air at or above which the

drive will run the supply fan at the maximum speed when cooling the conditioned space.

25

49c The percentage of full speed that the drive will run the supply fan when the temperature

difference is at or below the minimum value when cooling the conditioned space.