FanMaster Configuration and Start Up

3-7

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

8. Select the city with the climate profile closest to the installation location

(refer to

City Climate Profiles on page A-3

for a list of city values).

Press the up and down arrows (

) below the list to scroll to

and choose a city. City names are listed alphabetically, in order of North
America (U.S. then Canada), Europe, Central and South America, and
Asia.

Press Enter (

) to apply your selection. The selected city will be

highlighted.

If an acceptable climate profile is not included in the list, press “User
City” to access the User City Weather Data Setup screen (described on
page

C-14

) where you can create and save a climate profile for your

location. You must enter weather data as described in

City Climate

Data on page 1-9

.

9. Press the value to the right of the “Supply Fan HP” field and enter the

supply fan motor rated horsepower.

When a value field is pressed, a numeric keypad displays and the value
is editable. Use the keypad to type the desired value and press Enter to
accept the value. For fields with a decimal value, you must enter the
desired value for the field including the decimal value. For example: For
a value of 10.0, press “1”, “0”, “0”.

Press “Esc” to exit edit mode and cancel any edits.