Rockwell Automation FANM FanMaster Energy Saving Package User Manual

Page 28

Advertising
background image

2-10

FanMaster Installation

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

FanMaster Enclosure Weights

Lifting Instructions

The dimensions and weights provided above must be taken into
consideration when lifting and mounting the enclosure. Use the proper
equipment to safely lift and hold the weight of the enclosure while
mounting.

Mounting Instructions

1. Verify the hole pattern on the panel to which the enclosure will be

mounted. Refer to

Figure 2.3 on page 2-8

or

Figure 2.4 on page 2-9

.

2. For NEMA/UL Type 1 enclosures, insert, but do not fully tighten, one

bolt in one of the top holes in the panel. The bolt must be fully threaded
into the panel before hanging the enclosure.

3. For NEMA/UL Type 1 enclosures, lift the enclosure and place onto the

bolt installed in the panel.

4. Install the remaining bolts into the panel and fully tighten all bolts.

Enclosure

Enclosure Only Enclosure and Packaging

NEMA/UL Type 1

21.0 kg (46 lb)

26.3 kg (58 lb)

NEMA/UL Type 4

36.3 kg (80 lb)

41.7 kg (92 lb)

!

ATTENTION: To guard against possible personal injury or
equipment damage…

Inspect all lifting hardware for proper attachment before
lifting the enclosure.

Do Not allow any part of the enclosure or lifting mechanism
to make contact with electrically charged conductors or
components.

Do Not allow personnel or their limbs directly underneath the
enclosure when it is being lifted and mounted.