FanMaster Installation

2-17

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

16. (Optional - required when using the constant ventilation option rather

than the default demand ventilation option.) If FanMaster will be used
to control the outside air damper for constant ventilation control,
connect the damper position control wires to the appropriate terminals
on the drive.

Important: The analog output terminal used on the drive must be set

for a 4…20 mA signal only. Verify that the appropriate
drive DIP switch or jumper is properly set for a 4…20
mA signal or component damage may occur. Refer to the
appropriate drive User Manual for details. If the control
signal is 0…10V DC or 0…135 Ohms a converter adapter
must be purchased separately and be installed for both the
input and output signals.

For PowerFlex 400 drives, connect the damper position control
wires to terminals 14 (-) and 15 (+) in the drive.

For PowerFlex 70EC drives, connect the damper position control
wires to terminals 22 (-) and 23 (+) in the drive.

For PowerFlex 700VC drives, connect the damper position control
wires to terminals 6 (-) and 7 (+) in the drive.

For PowerFlex 753 drives, connect the damper position control
wires to terminals Ao0– and Ao0+ on TB1 in the drive.

17. (Optional - required when using the constant ventilation option rather

than the default demand ventilation option.) If FanMaster will be used
to override the BAS control of the outside air damper, connect the
damper position command signal wires to terminals 100, 102, 218 and
219 on TB2 in the FanMaster enclosure.

Important: Terminals 100, 102, 218 and 219 on TB2 of the

FanMaster unit accept a 4…20 mA signal only. If the
control signal is 0…10V DC or 0…135 Ohms, a
converter adapter must be purchased separately and be
installed for both the input and output signals.

18. For PowerFlex 400, style A, NEMA/UL Type 3R, 4 & 12 drives only,

jumper TB1-35 in the drive enclosure to drive signal terminal 8.

19. For PowerFlex 400 drives with full feature bypass only, connect

terminals 61 and 162 on FanMaster TB2 to terminals 34 and 36 on TB1
in the enclosure as shown.

20. For PowerFlex 400 drives with a full feature bypass and speed pot only,

install a new switch contact, part number 800F-X10, on the Hand Off
Auto switch in the “Auto” position. The switch snaps into place on the
second switch level on the right side of the switch as viewed from the
rear. Connect a wire from PF400 terminal 11 to the top of the switch.
Connect a wire from the bottom of the switch to PF400 terminal 8.
Verify that the switch contact closes when “Auto” is selected.