FanMaster Screens and Field Descriptions

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

Setup Screen #2

The second Setup screen is used to enter data required to configure the
FanMaster for your installation. This screen is different for evaluation unit
versus units installed with a drive. This configuration is completed at the
factory.

Table C.E Setup Screen #2 Fields

Field Name

Description

Drive Type

Type of drive installed. Choose the drive installed using the up or down and
Enter arrow buttons. (No selections are available for evaluation units.)

Heating Prop

Proportional (Heating Prop) or two-state (Heating 2-State) heating system
selection.

Cooling Prop

Proportional (Cooling Prop) or two-state (Cooling 2-State) cooling system
selection.

Pressure

FanMaster uses an optional pressure sensor (Pressure) or does not use
an optional pressure sensor (No Pressure) selection.

Demand Vent / Constant
Vent / Variable Vent

Demand ventilation (Demand Vent.), constant ventilation (Constant Vent.),
or Variable ventilation (no CO

2

) (Variable Vent.) mode selection.

Permanent Install Only

Evaluation Unit Install Only