Figure b.3, Fanmaster (w/drive) schematic diagram sheet 2a – Rockwell Automation FANM FanMaster Energy Saving Package User Manual

Page 78

Advertising
background image

B-4

FanMaster Diagrams

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

Figure B.3

FanMaster (w/Drive) Schematic Diagram Sheet 2A

Supply Air

Temp.

Analog Input

Expansion Module

#1762-IF4

Slot 1

(+24V DC)

100

TB2

100

+24V

IN 0(+)

IN 0(–)

(0V DC)

102

(0V DC)

102

Mixed Air

Temp.

CO2 Sensor

Damper Position

Command

from BAS or

Pressure Sensor

Signal Input

(Optional)

Signal

Com

Shld

123

102

124

123

125

IN 1(+)

IN 1(–)

127

IN 2(+)

IN 2(–)

218

IN 3(+)

IN 3(–)

Com

Com

100

Shld

125

102

126

+24V

Signal

Com

100

Shld

127

102

128

+24V

Signal

Com

+24V

Signal

Com

100

Shld

218

102

219

B

(From Sheet 1B)

B

(From Sheet 1B)

B

(From Sheet 1B)

Advertising