Rockwell Automation FANM FanMaster Energy Saving Package User Manual

Page 61

Advertising
background image

FanMaster Configuration and Start Up

3-25

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

60. Verify that the temperature transmitters and CO

2

sensor readings are

acceptable:

Insert a calibrated thermometer into the air duct where the mixed air
temperature transmitter is installed and compare the reading to the
value displayed in the “MAT (°F)” field on the Air Handler Unit
Diagram screen. The value in the “MAT (°F)” field should be
within +/- 5% of the of the value on the thermometer.

Insert a calibrated thermometer into the air duct where the supply
air temperature transmitter is installed and compare the reading to
the value displayed in the “SAT (°F)” field on the Air Handler Unit
Diagram screen. The value in the “SAT (°F)” field should be within
+/- 5% of the of the value on the thermometer.

Insert a calibrated carbon dioxide sensor into the air duct where the
CO

2

sensor is installed and compare the reading to the value

displayed in the “CO2 (ppm)” field on the Air Handler Unit
Diagram screen. The value in the “CO2 (ppm)” field should be
within +/- 5% of the of the value on the sensor.

Note: When the AHU cooling and heating elements are off but the
supply fan is running, the mixed air and supply air temperatures should
typically be within a few degrees of each other, indicating proper
calibration and operation.

Important: All instruments are calibrated at the factory. Follow the

manufacturer’s recommended calibration practices in order to
maintain the accuracy of the instruments.

You have successfully installed and configured the Allen-Bradley®
FanMaster™ Energy Saving Package.

If you want to

Refer to

View Detailed Data Log Information

page 3-26

Start or Stop Data Collection

page 3-27

Clear the Data Logs and Collect Data

page 3-28

Advertising