Figure b.11 on, Figure b.11, B-12 – Rockwell Automation FANM FanMaster Energy Saving Package User Manual

Page 86: B-12 fanmaster diagrams

Advertising
background image

B-12

FanMaster Diagrams

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

Figure B.11 Interconnect Diagram for PowerFlex 753 Drive - Sheet 1

FanMaster

TB2

TB3

TB1

TB2

TB2

Supply Fan Drive

PowerFlex 753

Drive TB2

R0NO

R0C

Drive Running

20-COMM-H TB

RS-485 cable

Signal = 120V AC

Signal = 4-20 mA

+

Optional Position
Command to Damper

Drive TB1

Ao0+

Ao0–

A.O. 0

A.O. 0 Com

PowerFlex 753

Signal = RS-485

Signal = 24V DC

Damper Position
Switch (In Econ. Mode)

BAS Outside Air
Damper Override Control

Black

Red

Line

Common

Signal = Customer Selected

Customer Supplied Line

Customer Supplied Nuetral

119

120

100

105

135

N

Fan Running Input

120V AC Input

L

N

G

Factory Installed Jumpers

Customer
Supplied
120V AC,
50/60 Hz
Power

Econ. Mode Switch +24V DC

Input Signal for Econ. Mode Switch

BAS Damper Override
Control Output

A

A

Notes:
1. All power, I/O and signal wire is customer supplied.
2. Non-shielded wires to be Belden No. 3105A or equal.
3. Shielded cable to be a Belden No. 3106A or equal.

Return Fan Drive

(Optional)

To Sheet 2

To Sheet 2

20-COMM-H TB

CGND

SHLD

COM

B

A

TERM

GND

SHIELD

COM

B

A

TERM

GND

SHIELD

COM

B

A

TERM

Advertising