FanMaster Configuration and Start Up

3-19

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

Note: When in cooling mode, the supply fan speed will typically be set
based on the difference in temperature (Delta-T) between the mixed air and
supply air (as illustrated, using default values, in

Figure 3.1

and

Figure 3.2

below) unless the supply air temperature exceeds the low limit override (is
less than the default value of 45° F). If the supply air temperature exceeds
the low limit override value, the fan speed will increase to the VFD output
maximum value (for cooling setup).

Figure 3.1

Example Two-State Cooling Setup

Figure 3.2

Example Proportional Cooling Setup

Delta-T

F

an Speed (%)

Two-State Cooling Setup

Delta-T

Min

Delta-T

Max

VFD
Output
Min

VFD
Output
Max

(Mixed Air - Supply Air Temp.)

10 20 30 40 50

100

75

50

25

0

Proportional Cooling

10 20 30 40 50

100

75

50

25

Delta-T

Min

Delta-T

Max

VFD
Output
Min

VFD
Output
Max

F

a

n Speed (%)

Delta-T

(Mixed Air - Supply Air Temp.)

0