3-22

FanMaster Configuration and Start Up

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

50. Below “Heating Setup”, enter the following values:

a. Press the value next to “Delta-T Min” and enter the difference in

temperature between the mixed air and supply air at or below which
the drive will run the supply fan at the minimum speed (set in the
corresponding “VFD Output Min” field) when heating the
conditioned space.

For two-state heating: When the difference in temperature rises

above the value set in this field, the supply fan will be
commanded to full speed (100% on).

For proportional heating: When the difference in temperature

rises above the value set in this field, the supply fan will ramp up
to a speed proportionate to the temperature difference.

b. Press the value next to “Delta-T Max” and enter the difference in

temperature between the mixed air and supply air at or above which
the drive will run the supply fan at the maximum speed (set in the
corresponding “VFD Output Max” field) when heating the
conditioned space.

For two-state heating: The value set in this field has no affect on

the fan motor speed and can be left set to the default value.

For proportional heating: When the difference in temperature is

below the value in this field, the supply fan will ramp up to a
speed proportionate to the temperature difference until the value
in this field is reached. Once the temperature difference in this
field is reached the fan speed will not exceed the value set in the
corresponding “VFD Output Max” field (typically 100%).

c.

Press the value next to “VFD Output Min” and enter the percentage
of full speed that the drive will run the supply fan when the
temperature difference is at or below the minimum value (set in the
corresponding “Delta-T Min” field) when heating the conditioned
space.

d. Press the value next to “VFD Output Max” and enter the percentage

of full speed that the drive will run the supply fan when the
temperature difference is at or above the maximum value (set in the
corresponding “Delta-T Max” field) when heating the conditioned
space.

51. The “Supply Air Low Limit” field, below “SA Low Limit Override”, is

used to set a supply air low temperature limit below which FanMaster
will run the supply air fan at full speed (100%) to avoid freezing up the
cooling system. Press the value next to “Supply Air Low Limit” and
enter the supply air low temperature limit at which FanMaster will
command the supply fan speed to run at full speed.