FanMaster Screens and Field Descriptions

C-7

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

Setup Screen #3

The third Setup screen is used to enter data required to configure the
FanMaster for your installation.

Table C.F Setup Screen #3 Fields

CO2

CO

2

sensor (CO2) or no CO

2

sensor (No CO2) installed selection.

AHU

Press to view the

Air Handler Unit Diagram Screen

.

Back

Press to view the

Setup Date and Time Screen

.

Next

Press to view the

Setup Screen #3

.

Field Name

Description

Field Name

Description

Does AHU Have Mech
Heating?

Mechanical heating (Yes) or no mechanical heating (No) system
installation selection.

Does AHU Have Mech
Cooling?

Mechanical cooling (Yes) or no mechanical cooling (No) system installation
selection.

Allow Outside Air
Damper Override for
Additional Savings?

FanMaster override of the BAS control (Yes) or no override of the BAS
control (No) of the outside air damper selection.

Override Duty Cycle %

Percent of time the outside air damper will be closed during a 20 minute
cycle time (when FanMaster is allowed to override). Valid values are
10…50%: 10% = 2 min. closed / 18 min. open, 50% = 10 min. closed / 10
min. open

Pressure Low Limit inWC Inches in Water Column value below which FanMaster will command the

Supply Fan speed to increase in order to maintain positive pressure in the
conditioned space.

CO2 Demand Setpoint
ppm

CO

2

parts per million (ppm) at which full fan speed and full outside air

ventilation occurs until the CO

2

level is 50 ppm below the value set in this

field.

CO2 Alarm Setpoint ppm CO

2

parts per million (ppm) at which the an alarm will display on the

PanelView screen, the fault indicator lamp on the front of the unit will turn
on and the FanMaster Faulted signal will be set to “Faulted”, indicating that
the high CO

2

level threshold has been exceeded.

AHU

Press to view the

Air Handler Unit Diagram Screen

.

Back

Press to view the

Setup Screen #2

.

Next

Press to view the

Supply Fan Setup Screen

.