Figure b.1, Fanmaster (w/drive) schematic diagram sheet 1a – Rockwell Automation FANM FanMaster Energy Saving Package User Manual
Page 76

B-2
FanMaster Diagrams
Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -
Publication FANM-IN001B-EN-P – December, 2009 PN-65329
Figure B.1
FanMaster (w/Drive) Schematic Diagram Sheet 1A
CB1
TB1
L
N
GND
10A
1
L
N
GND
Customer’s
Incoming
120V AC/60 Hz
1 Phase Power
L
N
G
L GND N
Power Supply
120V AC In / 24V DC Out
#1606-XLE120E PS1
(+24V DC)
100
CB2
5A
101
(+24V DC)
(0V DC)
102
Heater
Enclosure Heater
(NEMA/UL
Type 4 Only)
N
L
L2/N
GND
Serial
Port
E-Net
Port
PLC-MicroLogix 1100
#1763-L16BWA
PLC1
Crossover EtherNet Cable
E-Net
Port
1763-NC01 Modbus
Cable and Adapter
1
PanelView C600
GND
TB2
219
TB2
100
102
TB2
160
TB2
159
A2
A1
CR4
BAS Start from Building Controller
(24V AC or 120V AC)
TB2
162
TB2
161
11 14
CR4-1
Interposing Contact
for Customer Use or
for use with Full-Feature Bypass
(See Figure B.8 Interconnect Diagram - Sheet 1)
109
21 24
CR4-3
BAS Controller
Fan Start
100
(+24V DC)
102
(0V DC)
PanelView
*Note: 24V AC or 120V AC
from the BAS controller will
activate CR4, which provides
one contact to signal the
MicroLogix 1100 controller
to start FanMaster operation.
A second contact is
provided for customer use.
See
Note*
A
(To Sheet 1B)
A
(To Sheet 1B)
C
(To Sheet 2B)
C
(To Sheet 2B)
D
(To Sheet 1B)
TB3
TB2