FanMaster Installation

2-13

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

PowerFlex 70EC, 700VC or 753 Drive

Important: When installing a PowerFlex 753 drive, the 20-COMM-H

communication adapter requires the 20-750-20COMM
carrier option module.

Important: Leave the 20-COMM-H adapter rotary node address

switches set to “00” and set the network protocol switch
to “RTU”.

Important: The communication cable maximum length should not

exceed 500 m (1,640 ft).

a. For PowerFlex 753 drives only, install the 20-COMM-H, RS-485

HVAC adapter in the drive according to the installation instructions
in the 20-750-20COMM Option Card Installation Instructions,
publication 750COM-IN001.

b. Connect the 20-COMM-H adapter, via the RS-485 cable, to TB3 in

the FanMaster enclosure. Refer to the interconnect diagrams for the
PowerFlex 70EC (

Figure B.9 on page B-10

), PowerFlex 700VC

(

Figure B.10 on page B-11

) or PowerFlex 753 (

Figure B.11 on

page B-12

).

c.

Continue with step

10 on page 2-14

.

2

1

0

9

8

3

4

5

6

7

2

1

0

9

8

3

4

5

6

7

RTU