Rockwell Automation GV3000 AC Pwr Module Ver. 5.0 Hardware Ref, Installation, and Troubleshooting User Manual

Page 28

Advertising
background image

2Ć12

2.7.1 Jumper Locations and Settings

Jumpers J4 and J17 on the Regulator board are factoryĆset for voltage in and voltage out signals.

Refer to figures 2.8 and 2.9 for their locations on the Regulator boards. If you need to change the

jumpers' settings, use the following procedures.

CAUTION: Do not alter the setting of any jumper not described in this instruction manual. Failure to observe

this precaution could result in damage to or destruction of the equipment.

2.7.1.1 Analog Input Speed Reference Jumper

Jumper J4 is the analog speed/torque (U.000) reference jumper. This jumper selects either

+/- 10 VDC or 0Ć20 mA input. Parameters P.009, P.010, and P.011 are used in conjunction with the

jumper. Note that if the position of jumper J4 is changed after the parameters are programmed, the

software will not recognize that the input reference or polarity has been changed. Be sure to verify

that parameters P.009, P.010, and P.011 are correct before starting the drive. Refer to instruction

manual D2Ć3339 for more information.
Use the following procedure to set jumper J4:

DANGER

DĆC BUS CAPACITORS RETAIN HAZARDOUS VOLTAGES AFTER INPUT POWER HAS BEEN

DISCONNECTED. AFTER DISCONNECTING INPUT POWER, WAIT FIVE (5) MINUTES FOR THE DĆC

BUS CAPACITORS TO DISCHARGE AND THEN CHECK THE VOLTAGE WITH A VOLTMETER TO

ENSURE THE DĆC BUS CAPACITORS ARE DISCHARGED BEFORE TOUCHING ANY INTERNAL

COMPONENTS. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN SEVERE BODILY

INJURY OR LOSS OF LIFE.

Step 1. Turn off input power to the drive and wait five minutes.
Step 2. Remove the cover from the drive by unscrewing the four attaching screws.
Step 3. Verify that the DĆC bus voltage is zero by following the procedure in section 9.3.
Step 4. Locate jumper J4 on the Regulator board. Refer to figures 2.8 and 2.9.
Step 5. Locate pin 1 on jumper J4. Move the jumper to the desired setting as shown in figure 2.10.
Step 6. ReĆattach the cover.
Step 7. ReĆapply input power.
Step 8. Verify that Terminal Strip Analog Input Offset (P.009), Terminal Strip Analog Input Gain

(P.010), and Terminal Strip Analog Input Invert (P.011) are correctly set. Refer to instruction

manual D2Ć3339 for more information.

J4

J4

+10 VDC

Pins 2Ć3

Pins 1Ć2

0Ć20 mA

(default)

Voltage Input Option

Current Input Option

Figure 2.10 Ć Jumper J4 Settings for Analog Input Speed Reference

Advertising