Wiring the Output Status Relays
28
29
30
31
NormallyĆClosed Contact
(Form B)
NormallyĆClosed Contact
Common (Form B)
NormallyĆOpen Contact
(Form A)
NormallyĆOpen Contact
Common (Form A)
Both Form A and Form B contacts are rated for
250 VAC/30 VDC at 5 amps resistive or 2 amps inductive
load.
The following parameter must be set:
P.013: Output Relay Configuration
Note that depending on the setting of parameter P.013, the
relay coil will energize (the normallyĆopen contact will close
and the normallyĆclosed contact will open). Refer to the
GV3000 Programming instruction manual (D2Ć3339) for
more information.