Table A.1 Ć Service Conditions

AĆC Line Distribution System Capacity (maximum)

for 460 VAC Units

1000KVA, threeĆphase with 25,000 amps symmetrical

fault current capacity with a line impedance of less

than 8%

Control Method

AllĆdigital vector, sinusoidal pulseĆwidthĆmodulated

(PWM)

Displacement Power Factor

0.96

Line Frequency

50/60Hz (+2 Hz)

Line Voltage Variation

-10% to +10%

Line Dip Ride Through

Maximum 500 milliseconds Ć vector

Adjustable up to 999.9 seconds (See P.042) Ć V/Hz

Motor Lead Lengths

76 meters (250 feet) total

Analog Speed Reference Accuracy

0.5%

Acceleration Adjustment Range

0.1 to 999.9 seconds (within the ability of current)

Carrier Frequency

2 Hz, 4 Hz, or 8 Hz, softwareĆselectable

Current Limit Adjustment

U.006 to 150% (based on drive nameplate rating) Ć

vector

50% to 110% (based on drive nameplate rating) Ć V/Hz

Service Factor

1.0

Speed Adjustable Range

From 0 RPM to maximum speed

Speed Regulation

Vector Ć 0.01% long term steady state

V/Hz Ć motor slip dependent

Speed Reference Resolution

1 RPM with local keypad, -4095 to +4095 counts with

a network or serial reference

Torque Control Response

180 to 220 Hz

Torque Linearity

+3% with optimal parameter setting (typical) (see

parameter U.005)

Table A.2 Ć Ambient Conditions

Condition

Specification

Operating Temperature (Ambient)

0_ to +40_ C (32_ to 104_F)

Storage Temperature (Ambient)

-40_āto +65_C (-40_ to +149_F)

Humidity

5 to 95% (nonĆcondensing)