2Ć13

2.7.1.2 Analog Output Jumper

Jumper J17 is the analog output jumper. This jumper selects either a 0Ć10 VDC or 4Ć20 mA scaled

signal output that is programmable for either speed or torque, parameter P.012. The jumper only

selects a 0Ć10 VDC source voltage or 4Ć20 mA sink current to represent speed or torque. Note that

the 4Ć20 mA current selection requires a power supply for operation as shown in table 7.1, terminals

10 and 11.
Use the following procedure to set jumper J17:

DANGER

DĆC BUS CAPACITORS RETAIN HAZARDOUS VOLTAGES AFTER INPUT POWER HAS BEEN

DISCONNECTED. AFTER DISCONNECTING INPUT POWER, WAIT FIVE (5) MINUTES FOR THE DĆC

BUS CAPACITORS TO DISCHARGE AND THEN CHECK THE VOLTAGE WITH A VOLTMETER TO

ENSURE THE DĆC BUS CAPACITORS ARE DISCHARGED BEFORE TOUCHING ANY INTERNAL

COMPONENTS. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN SEVERE BODILY

INJURY OR LOSS OF LIFE.

Step 1. Turn off input power to the drive and wait five minutes.
Step 2. Remove the cover from the drive by unscrewing the four attaching screws.
Step 3. Verify that the DĆC bus voltage is zero by following the procedure in section 9.3.
Step 4. Locate jumper J17 on the Regulator board. Refer to figures 2.8 and 2.9.
Step 5. Locate pin 1 on jumper J17. Move the jumper to the desired setting as shown in figure 2.11.
Step 6. ReĆattach the cover.
Step 7. ReĆapply input power.
Step 8. Verify that parameter P.012 is set correctly for either speed or current.

J17

J17

+10 VDC

Voltage Output Option

Pins 2Ć3

Current Output Option

Pins 1Ć2

0Ć20 mA

(default)

Figure 2.11 Ć Jumper J17 Settings for Analog Outputs