Rockwell Automation GV3000 AC Pwr Module Ver. 5.0 Hardware Ref, Installation, and Troubleshooting User Manual
Page 93
![background image](/manuals/581361/93/background.png)
AĆ3
Table A.7 Ć Input Signal Response Times (Worst Case)
These are the maximum times from transitioning the input to the drive reacting to the input.
Signal Type and Source
Volts/Hertz Regulation
Vector Regulation
Keypad START
150 milliseconds
130 milliseconds
Terminal Strip:
START
126 milliseconds
105 milliseconds
STOP, RESET, FL
75 milliseconds
75 milliseconds
Preset Speeds
75 milliseconds
75 milliseconds
Analog Speed/Trim
Reference
16 milliseconds
5 milliseconds
Analog Torque Reference
N/A
0.5 milliseconds
Network:
START
46 milliseconds +network
transport time
25 milliseconds + network
transport time
STOP, RESET, FL
26 milliseconds +network
transport time
25 milliseconds + network
transport time
Analog Speed/Trim
Reference
5 milliseconds + network
transport time
5 milliseconds + network
transport time
Torque Reference
N/A
0.5 milliseconds + network
transport time