Rockwell Automation GV3000 AC Pwr Module Ver. 5.0 Hardware Ref, Installation, and Troubleshooting User Manual

Page 65

Advertising
background image

7Ć9

Table 7.1 Ć Wiring Signal and Control I/O to the Terminal Strip (Continued)

БББББ

Б

БББ

Б

БББББ

Terminal

Number

ББББББББББ

Б

ББББББББ

Б

ББББББББББ

Description

БББББББББББББББББББ

Б

БББББББББББББББББ

Б

БББББББББББББББББББ

Parameters/Wiring Connections

ББББББББББББББББББББББББББББББББ

ББББББББББББББББББББББББББББББББ

Wiring Analog Speed Reference Inputs

12

13

14

15

Isolated Reference

Voltage (+15VDC)
Analog Speed/Torque

Reference Input Voltage

(+/- 10 VDC)
Analog Speed/Torque

Reference Input Current

(0Ć20mA)
Isolated Speed/Torque

Reference Common

(Voltage/Current)

The following parameters must be set:

P.000: Control Source
P.009: Terminal Strip Analog Input Offset
P.010: Terminal Strip Analog Input Gain
P.011: Terminal Strip Analog Input Invert

Refer to the GV3000 Programming instruction manual

(D2Ć3339) for additional parameter information.

Jumper J4 must also be set. See figure 2.10.