Wiring a Forward/Reverse Input

19

Digital Input 6

(Default Ć Forward/Reverse)

Digital input 6 is control function programmable through

parameter P.007. The following parameters must be set:

P.000: Control Source
P.006: Second Menu Password
P.007: Terminal Strip Digital Inputs Configure (Selects

and assigns a control function to digital inputs 6

to 8).

P.008: Terminal Strip Speed Reference Source (Analog,

Motor Operated Potentiometer (MOP), or

Preset Speeds)

P.027: Reverse Disable

Note that based on the settings of parameters P.000, P.007,

P.008, and r.030 if an RMI board is used, the following

parameters can affect digital input 6.

P.023: MOP Accel/Decel Time
P.024: MOP Reset Configuration
P.031 to P.038: Preset Speeds 1Ć8

Refer to the GV3000 Programming instruction manual

(D2Ć3339) for additional information.

Terminal 19 On = Reverse Direction

Diagram shows factory setting. From the pulse tachometer

end of the motor, clockwise rotation indicates forward moĆ

tor movement.