Wiring Analog Outputs

10

11

0Ć10 VDC or 4Ć20 mA

Analog Output Reference
Regulator Common

The setting of parameter P.012 selects the terminal strip

analog output source (either speed or torque). Jumper J17

must also be set. See figure 2.11. The 4Ć20mA current

selection requires a power supply for operation. The power

can be sourced from the pulse tachometer supply, terminal

4 (15VDC), or from an external 15V power supply. Note that

the maximum supply current from terminal 4 is 250mA

(pulse tachometer and current source) at 15V. Terminals 9

and 11 are internally connected.

Terminal

Strip

+

Ċ

+

Ċ

+

Ċ

Load

(Meter or Analog Input)

Connection to the negative side of the

power supply is only required

when an external 15V power supply is used.