Table 7.1 Ć Wiring Signal and Control I/O to the Terminal Strip (Continued)
БББББББББББББББББББББББББББББББ
БББББББББББББББББББББББББББББББ
Wiring Analog Outputs
10
11
0Ć10 VDC or 4Ć20 mA
Analog Output Reference
Regulator Common
The setting of parameter P.012 selects the terminal strip
analog output source (either speed or torque). Jumper J17
must also be set. See figure 2.11. The 4Ć20mA current
selection requires a power supply for operation. The power
can be sourced from the pulse tachometer supply, terminal
4 (15VDC), or from an external 15V power supply. Note that
the maximum supply current from terminal 4 is 250mA
(pulse tachometer and current source) at 15V. Terminals 9
and 11 are internally connected.
Terminal
Strip
+
Ċ
+
Ċ
+
Ċ
Load
(Meter or Analog Input)
Connection to the negative side of the
power supply is only required
when an external 15V power supply is used.