9.4 Checking Out the Power Modules with Input Power Off

Use the following procedure to check the drive's Power Module circuitry with power off:

DANGER

DĆC BUS CAPACITORS RETAIN HAZARDOUS VOLTAGES AFTER INPUT POWER HAS BEEN

DISCONNECTED. AFTER DISCONNECTING INPUT POWER, WAIT FIVE (5) MINUTES FOR THE DĆC

BUS CAPACITORS TO DISCHARGE AND THEN CHECK THE VOLTAGE WITH A VOLTMETER TO

ENSURE THE DĆC BUS CAPACITORS ARE DISCHARGED BEFORE TOUCHING ANY INTERNAL

COMPONENTS. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN SEVERE BODILY

INJURY OR LOSS OF LIFE.

Step 1. Turn off and lock out input power. Wait five minutes.
Step 2. Remove the drive's cover.
Step 3. Verify that there is no voltage at the drive's input power terminals.
Step 4. Check the DĆC bus potential with a voltmeter as described in section 9.3 to ensure that the

DĆC bus capacitors are discharged.

Step 5. Disconnect the motor from the drive.
Step 6. Check all AĆC line and DĆC bus fuses.
Step 7. If a fuse is blown, use a multimeter to check the input diodes and output IGBTs. See table

9.1.
Note that 1Ć10HP drives do not have replaceable transistor modules: the entire drive must

be replaced if a transistor malfunctions. Intelligent Power Modules (IPM) may be replaced if

they fail in a 60Ć150HP drive.

Step 8. ReĆconnect the motor to the drive.
Step 9. ReĆattach the drive's cover.
Step 10. ReĆapply input power.

Table 9.1 Ć Resistance Checks

1Ć60HP Drives

Input

Diode

No.

Meter

Connection

(+)

(-)

Component is OK if

resistance (R) is:

Component is defective if:

1

ă*

R/L1

50 < R < 10 Megohm

Continuity (short circuit) or open when the meter is

connected with reversed polarity

2

ă*

S/L2

connected with reversed polarity

3

ă*

T/L3

4

R/L1

**

5

S/L2

**

6

T/L3

**

* (+) DĆC Bus Volts power terminal
** (-) DĆC Bus Volts power terminal