2 wiring requirements for the drive – Rockwell Automation GV3000 AC Pwr Module Ver. 5.0 Hardware Ref, Installation, and Troubleshooting User Manual

Page 37

Advertising
background image

3Ć5

3.1.4 Verifying Power Module Input Ratings Match Supplied Power

It is important to verify that plant power will meet the input power requirements of the GV3000 drive's

Power Module circuitry. Refer to table 2.1 for input power rating specifications. Be sure input power to

the drive corresponds to the drive nameplate voltage and frequency.

3.2 Wiring Requirements for the Drive

Certain drive requirements should be checked before continuing with the drive installation. Wire

sizes, branch circuit protection, speed feedback (for vector regulation), and EĆstop wiring (see

chapter 7), are all areas that need to be evaluated.

3.2.1 Meeting Terminal Strip Input and Output Specifications

The terminal strip on the Regulator board provides terminals for 24 VDC power for the eight remote

control inputs. Refer to tables A.3 and A.4 for control input and output specifications.

3.2.2 Determining Wire Size Requirements

Wire size should be determined based on the size of conduit openings, NEC/CEC regulations, and

applicable local codes.

DANGER

THE USER IS RESPONSIBLE FOR CONFORMING WITH ALL APPLICABLE LOCAL, NATIONAL, AND

INTERNATIONAL CODES. WIRING PRACTICES, GROUNDING, DISCONNECTS, AND

OVERCURRENT PROTECTION ARE OF PARTICULAR IMPORTANCE. FAILURE TO OBSERVE THIS

PRECAUTION COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.

3.2.2.1 Conduit Entry Opening Sizes

It is important to accurately determine the size of the conduit openings so that the wire planned for a

specific entry point will fit through the opening. Conduit opening sizes are shown in figures 4.1

through 4.6.

3.2.2.2 Recommended Power Wire Sizes

Input power wiring should be sized according to applicable codes to handle the drive's

continuousĆrated input current. Output wiring should be sized according to applicable codes to

handle the drive's continuousĆrated output current. See tables 3.3 through 3.7 for recommended

power wire sizes.

Table 3.3 Ć Recommended Power Wire Sizes for 1Ć10 HP Drives

Type of Wiring

Terminals

Size of Wire (Maximum)

AĆC Input Power

R/L1, S/L2, T/L3

Output Power

U/T1, V/T2, W/T3

12 AWG, 3 (mm

2

)

DĆC Input Power

+, -

12 AWG, 3 (mm )

Table 3.4 Ć Recommended Power Wire Sizes for 15Ć25 HP Drives

Type of Wiring

Terminals

Size of Wire (Maximum)

AĆC Input Power

R/L1, S/L2, T/L3

Output Power

U/T1, V/T2, W/T3

6 AWG, 13 (mm

2

)

DĆC Input Power

+, -

6 AWG, 13 (mm )