9.0 TROUBLESHOOTING THE DRIVE

This chapter describes how to troubleshoot the drive and the equipment that is needed to do so.

Also provided are replacement part lists and information on clearing faults.

9.1 Test Equipment Needed to Troubleshoot

An isolated multimeter will be needed to measure DĆC bus voltage and to make resistance checks.

9.2 Drive Alarms and Faults

The drive will display alarm and fault codes to assist in troubleshooting when a problem develops

during selfĆtuning or drive operation.
If an alarm condition occurs, the drive will continue to run and a 2Ć or 3Ćdigit alarm code will flash on

the display.
If a fault occurs, the drive will coastĆtoĆstop and a 2Ć or 3Ćdigit fault code will flash on the display.
Refer to the GV3000 Software StartĆUp and Reference Manual (D2Ć3339) for more information on

drive alarms and faults.

9.3 Verifying That DĆC Bus Capacitors are Discharged

DANGER

DĆC BUS CAPACITORS RETAIN HAZARDOUS VOLTAGES AFTER INPUT POWER HAS BEEN

DISCONNECTED. AFTER DISCONNECTING INPUT POWER, WAIT FIVE (5) MINUTES FOR THE DĆC

BUS CAPACITORS TO DISCHARGE AND THEN CHECK THE VOLTAGE WITH A VOLTMETER TO

ENSURE THE DĆC BUS CAPACITORS ARE DISCHARGED BEFORE TOUCHING ANY INTERNAL

COMPONENTS. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN SEVERE BODILY

INJURY OR LOSS OF LIFE.

The GV3000 drive's DĆC bus capacitors retain hazardous voltages after input power has been

disconnected. Perform the following steps before touching any internal components:
Step 1. Turn off and lock out input power. Wait five minutes.
Step 2. Remove the drive's cover.
Step 3. Verify that there is no voltage at the drive's input power terminals.
Step 4. Measure the DĆC bus potential with a voltmeter.

For 1Ć60 HP drives, measure the DĆC bus potential at the DĆC bus power terminals. See

figures 9.1 and 9.2.
For 60Ć100HP drives, while standing on a nonĆconductive surface and wearing insulated

gloves (600V), remove the top two screws of the regulator panel and tilt the panel forward.

See figure 9.3. Measure the DĆC bus potential at the diode bridge as shown. ReĆattach the

regulator panel.