Rockwell Automation GV3000 AC Pwr Module Ver. 5.0 Hardware Ref, Installation, and Troubleshooting User Manual

Page 67

Advertising
background image

7Ć11

Table 7.1 Ć Wiring Signal and Control I/O to the Terminal Strip (Continued)

БББББ

Б

БББ

Б

БББББ

Terminal

Number

ББББББББББ

Б

ББББББББ

Б

ББББББББББ

Description

БББББББББББББББББББ

Б

БББББББББББББББББ

Б

БББББББББББББББББББ

Parameters/Wiring Connections

ББББББББББББББББББББББББББББББББ

ББББББББББББББББББББББББББББББББ

Wiring an Additional Ramp Input

18

Digital Input 7

(Default Ć Ramp1/Ramp2)

Digital input 7 is control function programmable through

parameter P.007. The following parameters must be set:

P.000: Control Source
P.001: Accel Time 1 (Ramp 1)
P.002: Decel Time 1 (Ramp 1)
P.006: Second Menu Password
P.007: Terminal Strip Digital Inputs Configure (Selects

and assigns a control function to digital inputs

6 to 8).

P.008 Terminal Strip Speed Reference Source (Analog,

Motor Operated Potentiometer (MOP), or

Preset Speeds)

P.017: Accel Time 2 (Ramp 2)
P.018: Decel Time 2 (Ramp 2)

Note that based on the settings of parameters P.000, P.007,

P.008, and r.030 if an RMI board is used, the following

parameters can affect digital input 7.

P.023: MOP Accel/Decel Time
P.024: MOP Reset Configuration
P.031 to P.038: Preset Speeds 1Ć8

Refer to the GV3000 Programming instruction manual

(D2Ć3339) for additional information.

Terminal 18 On = Ramp 2

Diagram shows factory setting.