Rockwell Automation GV3000 AC Pwr Module Ver. 5.0 Hardware Ref, Installation, and Troubleshooting User Manual

Page 38

Advertising
background image

3Ć6

Table 3.5 Ć Recommended Power Wire Sizes for 25Ć60 HP Drives

Type of Wiring

Terminals

Size of Wire (Maximum)

A C Input Power

R/L1 S/L2 TL3

AĆC Input Power

R/L1, S/L2, TL3

Output Power

U/T1, V/T2, W/T3

2/0 AWG (2X), 185 (mm

2

)

DĆC Input Power

+, -

/

( ),

(

)

Table 3.6 Ć Recommended Power Wire Sizes for 60Ć100 HP Drives

Type of Wiring

Terminals

Size of Wire (Maximum)

A C Input Power

1L1, 1L2, 1L3

AĆC Input Power

1L1, 1L2, 1L3

2L1, 2L2

4/0 AWG, 95 (mm

2

)

Output Power

U, V, W

4/0 AWG, 95 (mm )

AĆC Ground

PE

2 AWG, 35 (mm

2

)

DĆC Input Power

45, 47

4/0 AWG, 95 (mm

2

)

DĆC Ground

6 AWG, 16 (mm

2

)

Table 3.7 Ć Recommended Power Wire Sizes for 100Ć150 HP Drives

Type of Wiring

Terminals

Size of Wire (Maximum)

A C Input Power

1L1, 1L2, IL3

AĆC Input Power

1L1, 1L2, IL3

2L1, 2L2

2/0 AWG (2X), 185 (mm

2

)

Output Power

U, V, W

2/0 AWG (2X), 185 (mm )

AĆC Ground

PE

4/0 AWG, 95 (mm

2

)

DĆC Input Power

45, 47

2 AWG, 35 (mm

2

)

DĆC Ground

6 AWG, 16 (mm

2

)

3.2.2.3 Recommended Control and Signal Wire Sizes

The recommended wire sizes to connect I/O signals to the terminal strip on the Regulator board are

shown in table 3.8. Recommend terminal tightening torque is 0.5 NewtonĆmeters (4.5 inĆlbs).

Table 3.8 Ć Recommended Terminal Strip Wire Sizes

Terminals

Wire Size

1 to 31

20 to 14 AWG, 2 to 0.5 (mm

2

)

3.2.2.4 Recommended Motor Lead Lengths

The following motor lead lengths are recommended to reduce line disturbances and noise. See

figure 3.3.
D For applications using one motor, motor lead length should not exceed 76 meters (250 feet).
D For applications with multiple motors, total motor lead length should not exceed 76 meters

(250 feet).

When total lead length exceeds 76 meters (250 feet), nuisance trips can occur. These trips are

caused by capacitive current flow to ground. Note that these capacitivelyĆcoupled currents should be

taken into consideration when working in areas where drives are running. If the motor lead length

must exceed these limits, output line reactors or other steps must be taken to correct the problem.

Note that drives set up for vector regulation can only be connected to one motor at a time.