Rockwell Automation GV3000 AC Pwr Module Ver. 5.0 Hardware Ref, Installation, and Troubleshooting User Manual
Page 38

3Ć6
Table 3.5 Ć Recommended Power Wire Sizes for 25Ć60 HP Drives
Type of Wiring
Terminals
Size of Wire (Maximum)
A C Input Power
R/L1 S/L2 TL3
AĆC Input Power
R/L1, S/L2, TL3
Output Power
U/T1, V/T2, W/T3
2/0 AWG (2X), 185 (mm
2
)
DĆC Input Power
+, -
/
( ),
(
)
Table 3.6 Ć Recommended Power Wire Sizes for 60Ć100 HP Drives
Type of Wiring
Terminals
Size of Wire (Maximum)
A C Input Power
1L1, 1L2, 1L3
AĆC Input Power
1L1, 1L2, 1L3
2L1, 2L2
4/0 AWG, 95 (mm
2
)
Output Power
U, V, W
4/0 AWG, 95 (mm )
AĆC Ground
PE
2 AWG, 35 (mm
2
)
DĆC Input Power
45, 47
4/0 AWG, 95 (mm
2
)
DĆC Ground
6 AWG, 16 (mm
2
)
Table 3.7 Ć Recommended Power Wire Sizes for 100Ć150 HP Drives
Type of Wiring
Terminals
Size of Wire (Maximum)
A C Input Power
1L1, 1L2, IL3
AĆC Input Power
1L1, 1L2, IL3
2L1, 2L2
2/0 AWG (2X), 185 (mm
2
)
Output Power
U, V, W
2/0 AWG (2X), 185 (mm )
AĆC Ground
PE
4/0 AWG, 95 (mm
2
)
DĆC Input Power
45, 47
2 AWG, 35 (mm
2
)
DĆC Ground
6 AWG, 16 (mm
2
)
3.2.2.3 Recommended Control and Signal Wire Sizes
The recommended wire sizes to connect I/O signals to the terminal strip on the Regulator board are
shown in table 3.8. Recommend terminal tightening torque is 0.5 NewtonĆmeters (4.5 inĆlbs).
Table 3.8 Ć Recommended Terminal Strip Wire Sizes
Terminals
Wire Size
1 to 31
20 to 14 AWG, 2 to 0.5 (mm
2
)
3.2.2.4 Recommended Motor Lead Lengths
The following motor lead lengths are recommended to reduce line disturbances and noise. See
figure 3.3.
D For applications using one motor, motor lead length should not exceed 76 meters (250 feet).
D For applications with multiple motors, total motor lead length should not exceed 76 meters
(250 feet).
When total lead length exceeds 76 meters (250 feet), nuisance trips can occur. These trips are
caused by capacitive current flow to ground. Note that these capacitivelyĆcoupled currents should be
taken into consideration when working in areas where drives are running. If the motor lead length
must exceed these limits, output line reactors or other steps must be taken to correct the problem.
Note that drives set up for vector regulation can only be connected to one motor at a time.