Rockwell Automation GV3000 AC Pwr Module Ver. 5.0 Hardware Ref, Installation, and Troubleshooting User Manual
Page 69

7Ć13
Table 7.1 Ć Wiring Signal and Control I/O to the Terminal Strip (Continued)
БББББ
БББББ
Terminal
Number
ББББББББББ
ББББББББББ
Description
БББББББББББББББББББ
БББББББББББББББББББ
Parameters/Wiring Connections
ББББББББББББББББББББББББББББББББ
ББББББББББББББББББББББББББББББББ
Wiring a Function Loss Input
20
Digital Input 5
(Function Loss)
The following parameters must be set:
P.026: Function Loss Response
A signal must be present at terminal 20 for the drive to be
able to start. See figures 7.1 and 7.2. The drive is shipped
from the factory with a jumper between terminals 16 and 20
which provides the signal. The function loss input should
be in series with the drive's external interlocks. In this case,
the jumper must be removed before the connections are
made. See figure 2.12.
Terminal 20 On = No Function Loss
(or from 16A and 20A on 15-60HP drives)
ББББББББББББББББББББББББББББББББ
ББББББББББББББББББББББББББББББББ
Wiring a Run/Jog Input
21
Digital Input 4
(Run/Jog)
The following parameters must be set:
P.000: Control Source
P.020: Jog Speed Reference
P.021: Jog Ramp Accel Time
P.022: Jog Ramp Decel Time
Terminal 21 On = Jog Operation