Rockwell Automation GV3000 AC Pwr Module Ver. 5.0 Hardware Ref, Installation, and Troubleshooting User Manual

Page 69

Advertising
background image

7Ć13

Table 7.1 Ć Wiring Signal and Control I/O to the Terminal Strip (Continued)

БББББ

БББББ

Terminal

Number

ББББББББББ

ББББББББББ

Description

БББББББББББББББББББ

БББББББББББББББББББ

Parameters/Wiring Connections

ББББББББББББББББББББББББББББББББ

ББББББББББББББББББББББББББББББББ

Wiring a Function Loss Input

20

Digital Input 5

(Function Loss)

The following parameters must be set:

P.026: Function Loss Response

A signal must be present at terminal 20 for the drive to be

able to start. See figures 7.1 and 7.2. The drive is shipped

from the factory with a jumper between terminals 16 and 20

which provides the signal. The function loss input should

be in series with the drive's external interlocks. In this case,

the jumper must be removed before the connections are

made. See figure 2.12.

Terminal 20 On = No Function Loss

(or from 16A and 20A on 15-60HP drives)

ББББББББББББББББББББББББББББББББ

ББББББББББББББББББББББББББББББББ

Wiring a Run/Jog Input

21

Digital Input 4

(Run/Jog)

The following parameters must be set:

P.000: Control Source
P.020: Jog Speed Reference
P.021: Jog Ramp Accel Time
P.022: Jog Ramp Decel Time

Terminal 21 On = Jog Operation