Detach from equipment phase (pdet) – Rockwell Automation 1794-Lxxxx PhaseManager User Manual

Page 102

Advertising
background image

102

Publication LOGIX-UM001B-EN-P - April 2010

Appendix A

Equipment Phase Instructions (PSC, PCMD, POVR, PFL, PCLF, PXRQ, PRNP, PPD, PATT, PDET)

Detach from Equipment
Phase (PDET)

Use the PDET instruction to relinquish ownership of an equipment phase.

Operands:

Relay Ladder

Structured Text

The operands are the same as those for the relay ladder PDET instruction.

Description:

After a program executes a PDET instruction, the program no longer owns the
equipment phase. This frees the equipment phase for ownership by another
program or by FactoryTalk Batch software. Use the PDET instruction only if
the program previously took ownership of an equipment phase via an Attach
to Equipment Phase (PATT). instruction.

Arithmetic Status Flags:

not affected

Fault Conditions:

none

Execution:

Operand

Type

Format

Description

Phase Name phase

name of the
equipment
phase

Equipment phase that you no longer want to
own

Condition

Relay Ladder Action

Structured Text Action

prescan

The rung-condition-out is set to false.

No action taken.

rung-condition-in is false

The rung-condition-out is set to false.

N/A

rung-condition-in is true

• The instruction executes.
• The rung-condition-out is set to true.

N/A

scan of structured text

N/A

In structured text, instructions execute each time
they are scanned. To limit the scan of an instruction,
use a qualifier of an SFC action and/or a structured
text construct.

instruction execution

The instruction relinquishes ownership of the
specified equipment phase.

The instruction relinquishes ownership of the
specified equipment phase.

postscan

The rung-condition-out is set to false.

No action taken.

Advertising
This manual is related to the following products: