Rockwell Automation 1794-Lxxxx PhaseManager User Manual

Page 74

Advertising
background image

74

Publication LOGIX-UM001B-EN-P - April 2010

Appendix A

Equipment Phase Instructions (PSC, PCMD, POVR, PFL, PCLF, PXRQ, PRNP, PPD, PATT, PDET)

Arithmetic Status Flags:

not affected

Fault Conditions:

none

Execution:

To clear the failure code, use a PCLF
instruction.

You must use a PCLF instruction to clear the failure code of an equipment phase. Instructions
such as a CLR or MOV won’t change the failure code. See Equipment Phase Clear Failure
(PCLF)
instruction on page 76.

Guideline

Details

Condition

Relay Ladder Action

Structured Text Action

prescan

The rung-condition-out is set to false.

No action taken.

rung-condition-in is false

The rung-condition-out is set to false.

N/A

rung-condition-in is true

• The instruction executes.
• The rung-condition-out is set to true.

N/A

scan of structured text

N/A

In structured text, instructions execute each time
they are scanned. To limit the scan of an instruction,
use a qualifier of an SFC action and/or a structured
text construct.

instruction execution

The instruction sets the value of the failure code for
the equipment phase.

The instruction sets the value of the failure code for
the equipment phase.

postscan

The rung-condition-out is set to false.

No action taken.

Advertising
This manual is related to the following products: