Appendix A

Equipment Phase Instructions (PSC, PCMD, POVR, PFL, PCLF, PXRQ, PRNP, PPD, PATT, PDET)

Execution:

Example:

Relay Ladder

Condition

Relay Ladder Action

Structured Text Action

prescan

The rung-condition-out is set to false.

No action taken.

rung-condition-in is false

The rung-condition-out is set to false.

N/A

rung-condition-in is true

• The instruction executes.
• The rung-condition-out is set to true.

N/A

scan of structured text

N/A

In structured text, instructions execute each time
they are scanned. To limit the scan of an instruction,
use a qualifier of an SFC action and/or a structured
text construct.

instruction execution

The instruction clears the NewInputParameters bit
of the equipment phase.

The instruction clears the NewInputParameters bit
of the equipment phase.

postscan

The rung-condition-out is set to false.

No action taken.

If ThisPhase.NewInputParameters = 1 (FactoryTalk Batch software has new input parameters for the equipment phase), then

DataValues[0] = 2. This sets the PXRQ instruction for transfer of control.

Send the Download Input Parameters Subset request to FactoryTalk Batch software. Because DataValues[0] = 2, the
instruction is set for transfer of control.

When RQ_Control[0].PC = 1 (The PXRQ instruction is done.), then

ThisPhase.NewInputParameters = 0 via the PRNP instruction.