Equipment Phase Instructions (PSC, PCMD, POVR, PFL, PCLF, PXRQ, PRNP, PPD, PATT, PDET)

Appendix A

Example:

Relay Ladder

Structured Text

In the prestate routine of an equipment phase…
(*If the drain valve does not go to the commanded
state, then set the failure code of this equipment
phase = 102.*)
If Drain_Valve.FaultAlarm Then

PFL(102);

End_If;

(*If the Drain_Tank equipment phase = running and
its failure code = 102, issue the hold command and
send the equipment phase to the holding state.*)
If Drain_Tank.Running And (Drain_Tank.Failure =
102) Then

PCMD(Drain_Tank,hold,0);

End_IF;

In the prestate routine of an equipment phase…
If Drain_Valve.FaultAlarm = 1 (The valve did not go to the commanded state.) then

Failure code for the equipment phase = 102.

If Drain_Tank.Running = 1 (The Drain_Tank equipment phase is in the running state.)
And Drain_Tank.Failure = 102 (failure code for the equipment phase)
Then

Change the state of the Drain_Tank equipment phase to holding via the hold command.