Pxrq error codes – Rockwell Automation 1794-Lxxxx PhaseManager User Manual

Page 86

Advertising
background image

86

Publication LOGIX-UM001B-EN-P - April 2010

Appendix A

Equipment Phase Instructions (PSC, PCMD, POVR, PFL, PCLF, PXRQ, PRNP, PPD, PATT, PDET)

PXRQ Error Codes

Arithmetic Status Flags:

not affected

Fault Conditions:

none

ERR (hex)

EXERR (hex)

Description

Recommended Action

00

0000

The PXRQ instruction was aborted before it
sent the request to FactoryTalk Batch
software.

None

01

0000

The PXRQ instruction was aborted after it
sent the request to FactoryTalk Batch
software.

None

02

0000

2 or more PXRQ instructions executed at the
same time using the same request type

Limit execution to 1 PXRQ instruction at a time.

03

0110

Communication error. The request was not
delivered because there is no subscriber
subscribed to the phase.

Check that FactoryTalk Batch software is connected and
running.

0210

Communication error. The request was not
delivered because there is no connection to
the Notify object.

Check that FactoryTalk Batch software is connected and
running.

0410

Communication error. Delivery failed.

Check the connection and communication path to
FactoryTalk Batch software.

1010

Communication error. The request was not
delivered because FactoryTalk Batch
software does not subscribe to receive the
external request.

Check that FactoryTalk Batch software is connected and
running.

1020

FactoryTalk Batch software isn’t attached to
the phase.

Check that FactoryTalk Batch software is attached to the
phase.

04

0002

The FactoryTalk Batch software
encountered an error while processing the
request.

Check the connection and communication path to
FactoryTalk Batch software.

0003

The PXRQ instruction contains an invalid
value.

Check the connection and communication path to
FactoryTalk Batch software.

0004

FactoryTalk Batch software is not in the
proper state to process the request.

Check the connection and communication path to
FactoryTalk Batch software.

0005

2 or more PXRQ instructions executed at the
same time using different request types

Limit execution to 1 PXRQ instruction at a time.

0006

Error storing to parameter tags at end of
request processing.

Check the connection and communication path to
FactoryTalk Batch software.

05

0000

FactoryTalk Batch software received the
request but passed back an invalid cookie.

Check the connection and communication path to
FactoryTalk Batch software.

06

0000

PXRQ instruction sent an invalid parameter
to FactoryTalk Batch software.

Check the connection and communication path to
FactoryTalk Batch software.

07

0000

Communication lost while PXRQ is waiting
for response from FactoryTalk Batch
software.

Check the connection and communication path to
FactoryTalk Batch software.

Advertising