Rockwell Automation 1794-Lxxxx PhaseManager User Manual

Page 81

Advertising
background image

Publication LOGIX-UM001B-EN-P - April 2010

81

Equipment Phase Instructions (PSC, PCMD, POVR, PFL, PCLF, PXRQ, PRNP, PPD, PATT, PDET)

Appendix A

Guidelines for Using the PXRQ Instruction

Configure the PXRQ Instruction

For more information about PXRQ requests, see FactoryTalk Batch
PhaseManager User's Guide, publication

BATCHX-UM010

.

Guideline

Details

Make sure to use an array for the
Data Values operand.

The Data Values operand requires a DINT array, even if the array contains only 1 element (that
is, the data type is DINT[1]).

In relay ladder, condition the
instruction to execute on a
transition.

This is a transitional instruction. Each time you want to execute the instruction, toggle the
rung-condition-in from false to true.

In structured text, use a construct
to condition the execution of the
instruction.

When you program a PXRQ instruction in structured text, consider the following:

• In structured text, instructions execute each time they are scanned.
• The PXRQ instruction updates its status bits only when it is scanned.

To keep the instruction from repeatedly executing but ensure that the status bits update,
enclose the instruction in a construct that:

• initiates the execution of the instruction only on a transition (change in conditions).
• remains true until either PC = 1 or ER = 1.

If You Want To

Then Configure The PXRQ Instruction As Follows

External Request

Data Value
Array Element

Value

download all input parameters

Download Input Parameters

DINT[0]

0

download a single input parameter

Download Input Parameters

DINT[0]

parameter ID

download a range of input
parameter

Download Input Parameters

DINT[0]

parameter ID of the first parameter

DINT[1]

number of values

download the input parameters
configured for automatic download
on start or transfer of control

Download Input Parameters Subset DINT[0]

start = 1
transfer of control = 2

download all output parameter
limits

Download Output Parameter Limits

DINT[0]

0

download a single output
parameter limit

Download Output Parameter Limits

DINT[0]

parameter ID

upload all reports

Upload Output Parameters

DINT[0]

0

upload a single report

Upload Output Parameters

DINT[0]

report ID

upload a range of reports

Upload Output Parameters

DINT[0]

report ID of the first report

DINT[1]

number of values

upload the output parameters
configured for automatic upload on
terminal state or transfer of control

Upload Output Parameters Subset

DINT[0]

terminal = 1
transfer of control = 2

Advertising